跳至主要内容

NAFCO | The Difference Between Brass Gate Valve and Brass Globe Valve

The Difference Between Brass Gate Valve and Brass Globe Valve
Time:2019-01-02 From: NAFCO | Brass Valves Manufacturer China
Brass gate valve and Brass globe valve are the two most commonly used shut-off valves. The main differences are:
1, the sealing surface is different
 When the Brass gate valve is opened and closed, the sealing surface of the valve core and the valve seat always contact and rub against each other, so the sealing surface is easy to wear, especially when the valve is close to the closed state, the pressure difference between the front and the rear of the valve core is large, and the sealing surface wear is more serious. When the valve flap of the shut-off valve is in the open state, its valve seat and the valve sealing surface are no longer in contact, so its sealing surface is less mechanically worn, but if the medium contains solid particles, it is easy to damage the sealing surface. . The sealing surface of the Brass gate valve has a certain self-sealing ability, and its valve core is tightly contacted with the sealing surface of the valve seat by the medium pressure, so as to be tight and not leaking. The wedge of the wedge Brass gate valve is generally 3 to 6 degrees, and the spool that is forced to close excessively or has a large temperature change is easily stuck. Therefore, the high-temperature, high-pressure wedge Brass gate valve has taken certain measures to prevent the valve core from being stuck in the structure. The sealing surface of the shut-off valve must be applied with a forced closing valve to achieve the seal. Under the same caliber, working pressure and the same driving device, the driving torque of the shut-off valve is 2.5~3.5 times of the Brass gate valve. This should be noted when adjusting the torque control mechanism of the electric valve. The sealing faces of the shut-off valves are only in contact with each other when they are completely closed, and the relative slippage of the forcibly closed spool and the sealing surface is small, so that the wear of the sealing faces is also small. The wear of the sealing surface of the shut-off valve is mostly due to the presence of debris before the valve core and the sealing surface, or due to the tightness of the closed state, resulting in high-speed flushing of the medium.
Brass gate valves China
2, the structure is different
    The Brass gate valve is more complex than the globe valve and has a large height. The Brass gate valve is shorter and higher than the shut-off valve. In particular, the open Brass gate valve requires a high height space, which should be noted in the case of limited installation space.
The structure of brass gate valve:
Structure of brass gate valves China
The structure of brass globe valve:
Structure of brass stop valves
3, Different flow resistance
When the Brass gate valve is fully open, the entire flow passage is straight through. At this time, the pressure loss of the medium operation is the smallest. Compared with the shut-off valve, its main advantage is that the fluid flow resistance is small, and the flow resistance coefficient of the ordinary Brass gate valve is about 0.08~0.12. The drag coefficient of the Brass globe valve is approximately 3.5 to 4.5. The opening and closing force is small. Brass Brass Brass gate valve are generally suitable for use, do not need to open and close frequently, and keep the ram fully open or fully closed, not suitable for adjustment and throttling. The flow resistance of the shut-off valve is large throughout the stroke, the unbalanced force is large, and the required driving force or torque is correspondingly much larger. However, it is well suited for use as a conditioning and throttling fluid. For high-speed flowing media, the ram can cause vibration of the valve under partial opening conditions, and vibration may damage the sealing surface of the ram and the valve seat, and throttling will cause the ram to be eroded by the medium.
Brass globe valves
4, different itinerary
the stroke of the Brass gate valve is larger than that of the shut-off valve.
5, the flow is different
When the shut-off valve is installed, the medium can enter from the bottom of the spool and enter from above. The advantage of the medium entering from below the spool is that the packing is not under pressure when the valve is closed, the life of the packing can be extended, and the packing can be replaced with the pressure in front of the valve. The disadvantage of the medium entering from the lower side of the valve core is that the driving torque of the valve is relatively large, about 1.05~1.08 times of the upper entry, the axial force of the valve stem is large, and the valve stem is easy to bend. For this reason, the medium enters from below, generally only for small-diameter shut-off valves (below DN50), and the shut-off valves above DN200 use the medium to flow in from above. Electric shut-off valves generally use a medium to enter from above. The disadvantage of the way the medium enters from above is exactly the opposite of the way it enters below. The flow direction of the Brass gate valve is the same from both sides. Compared with the Brass gate valve, the cut-off valve has the advantages of simple structure, good sealing performance and convenient manufacturing and maintenance; the disadvantage is that the liquid resistance is large, and the opening and closing forces are large.
6, the maintenance process is different
The maintenance of the Brass gate valve is not suitable for on-site pipelines, and the valve seat and disc of most of the shut-off valves can be replaced online without removing the entire valve from the pipeline. This is where the valve and pipeline are welded together. It is very suitable. Of course, the difference between the Brass gate valve and the Brass globe valve is more than these. In the selection and use, we must distinguish their similarities and differences in order to avoid mistakes. The application range of the Brass globe valve and Brass gate valve is determined according to its characteristics. In smaller passages, shut-off valves are often used when better shut-off sealing is required; in steam pipes and large-diameter water supply pipes, Brass Brass gate valve are used because fluid resistance is generally less demanding.
Forged brass gate valves
--------- The End ----------
This article is presented by NAFCO, all copyrights reserved.
NAFCO is a quality China brass valve manufacturer and supplier, with full line of brass valves China for your selection, such as brass ball valvesbrass gate valves,brass radiator valvesbrass angle valves, as well as relevant brass fittings. Please don't hesitate to contact us for any questions at support@acrofluid.com.

More articles of brass valves that you may be interested:

评论

  1. This is a really informative knowledge, Thanks for posting this informative Information. High-Performance Butterfly Valve

    回复删除

发表评论

此博客中的热门博文

NAFCO| What is magnetic lockable brass ball valve

What is the magnetic lockable brass ball valve?   The magnetic lockable brass ball valve, a type of brass ball valve that with magnetic device and key, has a function to prevent valve operation without permission, especially suitable for public places.     What is the structure of magnetic lockable brass ball valve?   The magnetic lockable brass ball valve included three parts: brass ball valve body, magnetic lock and valve key, as shown below:     How magnetic lockable brass ball valve works?    Brass ball valve is the main part to control the flow open or close, the magnetic lock is used to keep the valve stem from using, the valve keep is to take the magnetic lock off and on, also to switch the ball valve.   The brass ball valve at closing position, magnetic lock installed     The brass ball valve at open position, the magnetic lock removed     The valve key: one end is magnetic key for lock, the other is stem key for brass ball valve

NAFCO | Technical Requirements Should Attention When Purchasing Brass Valves

NAFCO | Technical Requirements Should Attention When Purchasing Brass Valves  From: NAFCO | Brass Valves China Manufacturer Today we talk about the technical requirements should attention when purchasing brass valves, it's extremely imoirtant to ensure every details before purchasing, to avoid any further problems after installation and uses.     1. The specifications and categories of brass valves should meet the requirements of the pipeline design documents   1.1 The model of the brass valve should indicate the national standard numbering requirements. If it is an enterprise standard, the relevant description of the model number should be indicated.   1.2 The working pressure of the brass valve requires ≥ the working pressure of the pipeline. Under the premise of not affecting the price, the working pressure of the brass valve should be greater than the actual working pressure of the pipeline; any side of the brass valve should be closed. Can withstand 1.1

NAFCO | Brass Safety Valves for Water Heater

New Brass Safety Valves for Water Heater Time:2019-04-03 From: NAFCO | Brass Valve Manufacturer China As a professional brass valve manufacturer, We NAFCO always keep research and developement of new products, to meet requirements from different customers' demands and applications, representing latest technology for brass valves such as brass ball valves, brass gate valves, radiator valves, brass fittings.   We newly develpoed a new seires of brass safety valve for water heater, specially designed low pressure water system, forged brass valve body,  rating pressure 0.8MPa   Overall View:     Front Side View:   Back Side View:   Inlet Size View:   With a cross design, to stop pipes or hoses getting inside, protect the valve structure and safety     Outlet Side View: With NBR seat for better seal and avoid leakage   What is a water heater safety valve?   The water heater brass safety valve is suitable for electric water hea